Specifications
Ballast
Type
Output
Level
Input
Power
(Watts)
Input
Current
(Apms)
Power
Factor
Current
THD %
Percent
Dimmed
Ballast
Factor
Ballast
Efficacy
F12800
120V
2 Lamp
Full
66
0.55
0.99
<10
Zero
0.90
1.36
Dimmed
30
0.25
0.99
70 %
0.31
1.03
F13800
120V
3 Lamp
Full
83
0.69
0.99
<10
Zero
0.75
0.90
Dimmed
44
0.37
0.99
70 %
0.32
0.72
F14800
120V
4 Lamp
Full
96
0.80
0.99
<10
Zero
0.64
0.66
Dimmed
36
0.30
0.99
76 %
0.15
0.42
F22800
277V
2 Lamp
Full
62
0.22
0.99
<20
Zero
0.86
1.39
Dimmed
30
0.11
0.97
70 %
0.32
1.06
F23800
277V
3 Lamp
Full
84
0.30
0.99
<15
Zero
0.78
0.93
Dimmed
31
0.11
0.94
70 %
0.32
1.03
F24800
277V
4 Lamp
Full
95
0.35
0.99
<15
Zero
0.65
0.68
Dimmed
35
0.13
0.95
76 %
0.14
0.40
Using F32T8 Lamps. Voltage is +/-10%. Lamp Crest Factor is <1.7